DIFFERENTIAL RELAY – Protection Relay

September 7, 2023
Technical
5 0

Author: Engr. Jahangir Amir

PROPERTIES OF DIFFERENTIAL RELAYS:

  • Use for power transformers protection
  • It responds to vector differences (phase/magnitude) between two or more similar electrical quantities
  • The difference flows through the operating coil during any abnormal fault conditions
  • Differential relay asses only the amount of current flowing, when ‘I’ exceeds it gives out tripping signal.
  • It is non directional relay
  • It works on the basis of difference of current
  • It differentiate between fault and healthy condition
  • Differential Zone is between HV-CT to LV-CT
Diffential Relay Connection Diagram
Differential Relay Current Flow Diagram

WORKING OF DIFFERENTIAL RELAYS:

  1. IT SHOULD OPERATE:
  • It Should Operate If Current Is Increased From Its ‘Present Value’, Immediately
  • It Should Operate When Fault in Differential Zone.

2. IT SHOULD NOT OPERATE:

  • It should not operate (stable) on inrush current, when transformer is energized/switching
  • It must not operate during through fault (fault outside the differential zone)
  • It must not operate in any overload conditions

3. IT CAN CLEAR THE FOLLOWING FAULTS:

  • Any sudden fault on the jumpers from 132 kV CT to breaker, lighting arrestors
  • 132 or 11kV lighting arrestor may damage
  • Any phase to phase or phase to earth short circuit faults within the body of the transformer
  • There may be fault in 11 kV PT/CT or any incoming cables

TESTING OF DIFFERENTIAL RELAYS:

  1. PICK-UP TEST:         
  • For testing the performance of relay
  • Test the tripping on setting values

2. SLOP or BIASING TEST (BALANCING):

Checking the balancing of differential relay

  • Is It Operating On Zone Fault?
  • Is It Stable (Not Operate) On Through Fault (Out Of Zone Fault)?
  • Is It Stable On On-Load Tap Operation?

3. 2ND HARMONIC RESTRAINT TEST (INRUSH CURRENT):     

  • Check The Relay Stability On Inrush Current/ 2nd Harmonic
  • When Power Transformer Is Energized, Inrush Current Produced, Due To Inrush Current 2nd Harmonic Produced In The Transformer.

4. BEHAVIOR ON INRUSH CURRENT:

  • At the time of switching heavy inrush current flow into the primary of t/f, secondary side is still open and no current flow in it.
  • It may be 6 times of rated current
  • Bias winding provide protection from inrush current

5. HARMONIC RESTRAINED:

  • This relay also provides a harmonic restraint features.
  • During inrush currents several harmonic currents may also flow. (2nd to 7th ) Restrained Coil/Biasing Winding Is Used In Differential Relay For Preventing The Tripping On Inrush Current

TYPES OF DIFFERENTIAL RELAY:

  • Simple Over Current Differential Relay
  • %Age Biased Differential Relay

EXAMPLES OF DIFFERENT DIFFERENTIAL RELAYS:

  • SIEMENS         SIPROTEC, 7UT7250, 7UT5125,
  • ABB                 SEAD346C
  • GEC                 DMH,DTH,
  • ASEA               RXD3B4, RXDSD4,
  • AEG                 RX4A
  • BBC                 D21SE2

Leave a Reply

Your email address will not be published. Required fields are marked *

Open chat
1
Hello,
How can I help you?