Author: Engr. Jahangir Amir
- PROTECTION OF POWER TRANSFORMER
- DIFFERENTIAL RELAY:
- Differential Zone (High Voltage – Current Transformer to Low Voltage -Current Transformer, Clear all fault Between them.
- OVER CURRENT & EARTH FAULT RELAY:
- None Directional Relay , Their Zone is the Circuit / Equipment On Which Installed
- MAIN BUCHHULZ RELAY & TAP BUCHHULZ RELAY:
- Detect the failure of the winding insulation will result in some form of arcing, which can decompose the oil into hydrogen, acetylene, methane, etc. localized heating can also precipitate a breakdown of oil into gas.
- Detects the Incipient (Early Stage) Fault in the Transformer
- It has Ability to Retain the Gas Developed within the Transformer After A Fault.
- It has Two Contacts, One For Alarm And Other For Trip.
- WINDING TEMPERATURE GAUGE & OIL TEMPERATURE GAUGE:
- Watches the Winding and Oil Temperature of the Transformer
- It has Three Contacts, which Operates at Three Temperature Settings Respectively;
- 65*C Fans Start, 55*C Fans Off
- 90*C Alarm On 80*C Alarm Reset
- 100*C Trip Signal 90*C Trip Signal Reset
- Note: Oil Temp: Also has Three Settings, But each 10*C Less.
- PRESSURE RELIEF DEVICE:
- On Severe Faults, Certain Pressure Develops in the Transformer Tank, Such as Explosion Vent Or Pressure Relief Valve.
- RESTRICTED EARTH FAULT RELAY:
- To Protect the Transformer from Earth Faults within the Windings,
- It is Especially Required when Transformer is Resistance Or Impedance Earthed
- OVER FLUXING OR OVER EXCITATION:
- Voltage Rise of the Transformer Supply (Load Drop)
- NEUTRAL / BODY GROUNDING :
- Protection from the Heavy Fault Current
- LIGHTING ARRESTOR (132 & 11 KV) :
- Preventing from Lightening
- TESTING OF POWER TRANSFORMER
- WINDING RESISTANCE TEST (MEGGER):
- 15 Seconds = R15 (Form Factor =R60/R15)
- 60 Seconds = R60
- C&DF OF TRANSFORMER & BUSHING:
- Measurement Of Capacitance And Dissipation Factor Of The Insulation System Of Windings And Bushing ( For Minor Fault In Major Insulation)
- TTR, TRANSFORMER TURN RATIO:
- Measurement Of Voltage Ratio
- Check The Phase Displacement
- OPEN CIRCUIT OR NO LOAD TEST:
- To Determine No-Load Loss Or Core Loss And No-Load ‘I’ Which Is Helpful In Finding X And R
- SHORT CIRCUIT OR IMPEDANCE TEST:
- It Is Economical Method For Determining The Following;
- Copper Loss At Full Load ( And At Any Desired Load), This Loss Is Used In Calculating The Efficiency Of The Transformer
- Equivalent Impedance Z, Leakage Reactance X And Total Resistance R Of The Transformer As Referred To The Winding In Which The Measuring Instruments Are Placed
- Total Voltage Drop In The Transformer As Referred To Primary Or Secondary Can Be Calculated And Hence Regulation Of The Transformer Determined
- It Is Economical Method For Determining The Following;
- WINDING INSULATION RESISTANCE TEST:
- Primary Winding To Secondary Winding
- Primary Winding To Earth
- Secondary Winding To Earth
- OIL INSULATION TEST:
- Dielectric Strength Of Oil
- Efficient Heat Transfer And Cooling
- To Preserve The Core And Assembly
- SEQUENCE IMPEDANCE (Z1, Z2, Z0 ):
- Positive And Negative Sequence Impedances (Z1 And Z2) Of A Transformer Are Identical
- Zero Sequence Impedance (Z0) Is Dependent Upon The Path Available For The Flow Of Zero Sequence Current And The Balancing Ampere Turns Available Within The Transformer
- PERCENTAGE IMPEDANCE, Z%:
- The %Z Of A Transformer Is The Volt Drop On Full Load Due To The Winding Resistance And Leakage Reactance Expressed As A Percentage Of The Rated Voltage,
- It Is Also The Percentage Of The Normal Terminal Voltage Required To Circulate Full-Load Current Under Short Circuit Conditions